MCS 1800 Power Systems

  • Compact Power Plant
    Increased power density and design flexibility allow the system to grow with up to four modules in one shelf.
  • Uninterrupted Operation
    Rectifier modules may be added to the system without interruption of service. As demand increases, plug-in rectifiers enable the system's growth without the need for additional system wiring.
  • Remote Management
    The MCS-1800 power shelf is equipped with both an RS-232 direct connect/modem and RJ-45 Web Interface for local or remote monitoring and control. This functionality offers system management tools over Internet/Intranet environments.

SPECIFICATIONS

POWER SHELF
System Capacity 48VDC: -48VDC / 30A - 180A (48VDC / 30A rectifier x 1 - 6)
24VDC: +24VDC / 50A - 200A (24VDC / 50A rectifier x 1 - 4)
AC Input 90 - 275VAC, single-phase
Operating Temperature +32°F to +122°F (0°C to +50°C)
Storage Temperature -40°F to +158°F
(-40°C to +70°C)
Humidity 0 - 95% non-condensing
RECTIFIER
INPUT
Input Voltage 176 – 275VAC (100% load), single-phase
151 – 175VAC (80% load)
90 – 150VAC (50% load)
Input Current <12A (low line input, full load)
Line Frequency 45 – 65Hz
Power Factor >0.99, 220VAC, full load
THD
<5%, 220VAC, full load
Efficiency ≥90% for ESR-48/30B @ full load, 220VAC
≥88% for ESR-24/50D @ full load, 220VAC
OUTPUT
DC Output Voltage ESR-48/30B: 40 – 60VDC
ESR-24/50D: 20 – 29VDC
Output Power

ESR-48/30B: 1800W (0°C to +50°C)
1500W (+50°C to +65°C)
ESR-24/50D: 1500W (0°C to +50°C)
1200W (+50°C to +65°C)

Regulation
Load
Line
< ± 0.5%
< ± 0.1%
Current Limit 110% of rated output current
Noise Audio Band
Wide Band
Acoustic
< 2mV CCITT
<20mVrms (10KHz – 100MHz)
<55dBA @ 1M