1200 Amps @ -48VDC
2400 Amps @ +24VDC
SYSTEM ARCHITECTURE | ||
System Type | Maximum Power | Maximum Current |
+24V** | 67.2kW | 2808A |
-48V | 72kW | 1500A |
** -48V DC/DC converters available for +24V solution | ||
RECTIFIER | ||
INPUT | +24V | -48V |
Voltage, nominal (V rms) | 220 | 220 |
Voltage Range (V rms) | 90-300 | 90-300 |
Reduced Power (V rms) | 90-176 | 90-176 |
Current maximum (A rms) |
18 | 19 |
Frequency (Hz) | 45-65 | 45-65 |
Power Factor | 0.99 | 0.99 |
THD (%) | <5 | <5 |
OUTPUT | ||
Voltage, nominal (VDC) | 27 | 54 |
Voltage Adj. Range (VDC) | 20-29 | 40-59.5 |
Power Limitations (W) | 2800 | 3000 |
Current Limitations (A) | 116.6 | 62.5 |
Efficiency (%) | 89.5 | 91 |
MECHANICAL | ||
Dimensions (W x H x D) |
5.4” x 3.3” x 15.2”/138mm x 84mm x 385mmColor | |
Weight | 11 lbs. / 5kg | |
SAFETY & ENVIRONMENT | ||
Safety Standards | IEC 60950 EN 60950 UL 60950 |
|
Protection Class | IP20 | |
EMC | EN55022 Class B FCC Part 15 Class B |
|
Operating Temperature |
-4°F to +149°F (-20°C to +65°C) | |
Reduced Power | +122°F to +149°F (+50°C to +65°C) | |
Cooling | Forced air cooling, front to rear | |
Relative Humidity, maximum (%) |
95, non-condensing |