165P Power System

10,000 Amps @ -48VDC

  • 10,000 Amp & 6,000 Amp bus versions
  • Controlled ferroresonant rectifiers
  • Digital meter and alarm panel
  • Optional NetMACS™ monitoring system
  • Various distribution panels with fuses or circuit breakers
  • Internal bay interconnect bus
  • Unique plant design and internal bus structure reduces installation time
  • Can be installed for left or right expansion
  • Distribution bays are segregated from battery and rectifier termination bays for controlled system architecture

SPECIFICATIONS

INPUT
Voltage Range Refer to selected rectifier specifications
Frequency Refer to selected rectifier specifications
OUTPUT
Voltage Range 48 – 60VDC
Current 400A charge capacity
per rectifier
ENVIRONMENTAL
Storage Ambient


-40°F to +185°F
(-40°C to +85°C)
Operating Ambient 32°F to 86°F
(0°C to +30°C)
Humidity < 95% non-condensing
MECHANICAL
Dimensions,
Fully Equipped


84”H x 36”D x 30”W
Weight 965 lbs. maximum per bay
Cooling Convection
DOCUMENTATION
Product Manual
4380138PD
J Drawing J-438165P
About PECO II | Investor Relations | Contact Us | News & Events | Employee Login
Home | Products | Services | Document Downloads
Copyright © 2010 PECO II by Lineage Power