24V and 48V DC Power Plant
INPUT | +24V | -48V |
Voltage Range | 175 – 275VAC Nominal 208 / 240VAC |
|
Voltage Range, Low Line |
85 – 140VAC Nom 110/120VAC |
N/A |
Frequency | 45 – 66Hz | |
Current | 14.9A @ 208VAC, 12.9A @ 240VAC |
14.5A @ 208VAC, 12.6A @ 240VAC |
Customer Provided Protection | 20A CB per rectifier | |
OUTPUT | ||
Voltage Range | 21 – 29VDC | 42 – 58VDC |
Current | 100A per rectifier | 50A per rectifier |
Efficiency (Rectifier) | > 90% full load | > 96% full load |
Efficiency (Converter) | > 90% full load | > 90% full load |
NOISE | ||
Voice Band | < 32dBrnc (with battery) | |
Wide Band | ≤ 100 mVrms (10 – 20MHz)/ < 250 mV peak to peak (0 – 100MHz) |
|
Acoustic | < 55dB | |
Total Harmonic Distortion | > 5% at full load | |
ENVIRONMENTAL | ||
Storage Ambient | -40°F to +185°F (-40°C to +85°C) | |
Operating Ambient | -40°F to +167°F (-40°C to +75°C) | |
Humidity | < 95% non-condensing | |
Heat Dissipation Per rectifier |
930 BTU/hr | 745 BTU/hr 371 BTU/hr in 2010 |
Per converter | 615 BTU/hr | 490 BTU/hr |
MECHANICAL | STANDARD | EXTENDED |
Dimensions, Fully Equipped | 36.8"H x 22”D x 23" mounting width | 45.5"H x 22"D x 23" mounting width |
Weight (approx) | 450 lbs. | 590 lbs. |
Shelf Weight | 15.1 lbs / 6.85 kg | |
Rectifier Weight | 5.2 lbs / 2.4 kg | |
Cooling | Front to rear variable speed fans | |
SAFETY & COMPLIANCE | ||
Safety Standards | ETL Listed to UL 60950-1-07 CAN/CSA C22.2 No. 60950-1-07 |
|
NEBS Certified | ||
DOCUMENTATION | ||
Product Manual | 4380478PD | |
J Drawing | 438138-9LP | |
Phoenix II Manual | 4380405PD | |
Quick Start Guide | 4380403P |