Up to 400 Amps @ -48VDC
INPUT | |
Voltage Range | 176-275VAC single phase |
Frequency | 45 - 65Hz |
Current | 13A AC typical, 19A AC maximum per rectifier |
Customer Provided Protection | 25A, 2-Pole CB per rectifier |
OUTPUT | |
Voltage Range (-48VDC) | 42 - 59.5VDC, 54.0VDC nominal |
Current (-48VDC) | 50A per rectifier 400A per system |
Efficiency | 92% full load |
NOISE | |
Voice Band |
< 32dBrnc (with battery) |
Wide Band | < 100 mVrms (10 - 20MHz) / < 250 mV peak to peak (0 - 100MHz) |
Acoustic | < 55dB |
ENVIRONMENTAL | |
Storage Ambient |
-40°F to +185°F (-40°C to 85°C) |
Operating Ambient | +23°F to +122°F (-5°C to +50°C) |
Humidity | < 95% non-condensing |
Heat Dissipation | 750 BTU/hr per rectifier module at full load |
MECHANICAL | |
Dimensions, Fully Equipped |
17.5˝H x 19.0˝W or 23.0˝W x 22.0˝D |
Weight | 450 lbs. |
Cooling | Front to rear fans in rectifer module |
DOCUMENTATION | |
Product Manual |
4380442PD |
J Drawing | 438129NP |