Distribution Panels

  • Available with alarmed circuit breakers or fuses
  • Fuse panels can be equipped with GMT, KLM, Type-70, TPA, or a combination of fuses
  • Panels mount in 19" or 23" relay racks, or system cabinets
  • Every panel is put through an intense quality inspection and testing process
  • CSA certified & CE compliant

ALARM BOARD OPTIONS

  • Alarm Board A Provides status LED and wire wrap pins for alarm outputs. A blown fuse on either A or B will cause a front panel LED indication and provide three sets of form C contacts to extend the visual, audible, and remote alarms through the rear of the panel on wire wrap pins; labeled as NO (normally open), NC (normally closed), and C (common).
  • Alarm Board B Provides four LEDs and wire wrap pins for alarm inputs and outputs. A blown fuse on either A or B will cause the green LED to go out and the red A or B “Fuse Fail” LED to turn on. It will also make the Major Alarm relay de-energize, causing the Major Alarm relay contacts to close. When the Major or Minor Alarm is extended to the input pins, the Major or Minor Alarm relay is de-energized. The Major or Minor relay contacts are closed, the green LED is off, and the amber “Aux Alarm” LED turns on.