5069HC BDFB/BDCBB

6 Load, 1000 Amps Per Load

  • 1000 Amp load centers – From one to six panels with a capacity from 1000 to 6000 Amps per bay
  • High capacity distribution – Up to 6 loads with 144 single slot positions designed for 1-125 Amp fuses or 2-100 Amp CB’s; double slot receptacles can support up to 250 Amp positions
  • Fuse and circuit breaker distribution – Bullet style TPC, TPW, TPS, and TLS type fuses; plug-in style breakers, single, double and triple pole versions available with a maximum of 144 positions
  • Modular design – Allows for factory or field configured panels for scalable growth and reduced first costs
  • Redundant alarming – Power is continuously provided to the alarm circuits until the last bus no longer has power available
  • Digital metering of all load centers – Discretionary selector switch allows for viewing of current and voltage for each load center

PRODUCT DESCRIPTION

The 5069HC is a high capacity DC distribution product designed to serve offices with concentrated large loads, such as IP routers or optical multiplexers. The 5069HC provides 1000 to 6000 Amp requirements all within the same foot print. Utilizing bullet-style receptacles, output circuits of 1-250 Amps can be added as needed without tools. This highly versatile product can be equipped with as few as two and as many as six distribution panels allowing the user to lower the implementation costs of the initial and future installation visits. Additionally, the 5069HC can be purchased or field wired from a 2 to 4 or 6 load bay. Fully rated at 1000 Amps per load, the 5069HC provides industry leading capacity designed to support existing and future DC requirements.

  • Distribution options are user defined based on the requirement; single, double and triple pole circuit protectors can be combined in any of the distribution panels
  • The 84"H x 15"D x 26"W foot print allows for discretionary placement designed to meet most any equipment aisle arrangement
  • The meter panel allows the user to select and view both current and voltage of each distribution load. Additionally, test jacks on the meter panel provide for greater detail and diagnostics
  • The bay alarm panel extends an FA alarm if a protection device trips, blows, or otherwise fails. Visual notification of alarm(s) is provided via an LED. A power loss alarm is also extended from the BDFB.
About PECO II | Investor Relations | Contact Us | News & Events | Employee Login
Products | Services | Solutions | Document Downloads
Copyright © 2010 PECO II by Lineage Power