827E Inverter System

  • -48V input, scalable up to 28.8KVA @ 120VAC
  • +24V input scalable up to 3600VA @ 120VAC
  • Hot-swappable, redundant inverter modules
  • Modular design lowers installed first costs
  • Compact depth of 15" allows for large range of
    placement options
  • True sine wave output
  • Voltage THD less than 3%
  • Patented forced load share without LSO
  • Quickly back up and restore system configuration
  • Dial-up access with optional modem
  • Optional equipment includes Maintenance Bypass, AC Distribution panel

SPECIFICATIONS

INPUT -48V +24V
Voltage Range -42 – 60VDC +21 to +32VDC
Current 35Amps per inverter module 35Amps per inverter module
Recommended input fuse/Breaker per inverter module 50/40 50/40
OUTPUT
Voltage 120VAC 120VAC
Frequency 60Hz 60Hz
Current 1200W per inverter
7200W per shelf
28.8KW per system
600W per inverter
3600W per shelf
3600W per system
ENVIRONMENTAL
Storage Ambient
to 4800 ft.
-40°F to +185°F
(-40°C to +85°C)
-40°F to +185°F
(-40°C to +85°C)
Operating Ambient
to 4800 ft.
-40°F to +149°F
(-40°C to +65°C)
-40°F to +149°F
(-40°C to +65°C)
Humidity < 95% non-condensing < 95% non-condensing
Heat Dissipation (BTU/hr per inverter module at full load) 778
389
MECHANICAL
Inverters per shelf 4 / 6 4 / 6
Total Shelves 4 1
Dimensions,
Fully Equipped
8.75"H x 15"D x 19" or 23" 8.75"H x 15"D x 19" or 23"
Weight 74 lbs. 61 lbs.
Cooling Front to rear fans in inverter modules Front to rear fans in inverter modules
DOCUMENTATION
Product Manual
4380419PD 4380419PD
J Drawing 438827E 438827E
About PECO II | Investor Relations | Contact Us | News & Events | Employee Login
Home | Products | Services | Document Downloads
Copyright © 2010 PECO II by Lineage Power